HARTWERKPOWER
Fire-safe, maintenance-free power for indoor and underground installations.

Cast Resin Dry-Type Transformer

Fire-safe, maintenance-free power for indoor and underground installations.

Safety Without Compromise

Safety Without Compromise

Hartwerk Power cast resin transformers are designed for environments where fire safety and environmental protection are non-negotiable. Using Class F or Class H insulation systems with epoxy resin encapsulation, these units operate without cooling liquid — eliminating the risk of leaks and fire propagation.

Ideal for data centres, metro systems, hospitals, and offshore platforms where space is constrained and safety regulations are stringent. Every unit is vacuum-cast under controlled conditions to eliminate air voids, ensuring partial discharge below 5 pC across the winding.

Key Features

Fire-Safe Design

Self-extinguishing epoxy resin. Zero liquid dielectric — no fire propagation risk.

Low Partial Discharge

Vacuum-cast process ensures PD levels under 5 pC for extended insulation life.

Overload Capable

Designed for 150% overload for 30 minutes without degradation.

Zero Environmental Risk

No oil, no containment bunds required. Compliant with the strictest environmental codes.

Technical Specifications

Power Range100 kVA — 25 MVA
Primary VoltageUp to 36 kV
Insulation ClassF (155 °C) / H (180 °C)
CoolingAN (Air Natural) / AF (Air Forced)
StandardsIEC 60076-11, ANSI/IEEE C57.12.01
EnclosureIP00 — IP54

Applications

Data Centres

Compact footprint, fire-safe construction, and low noise for co-location with server racks.

Underground Metro

Zero oil risk in confined underground spaces with stringent fire regulations.

Offshore Platforms

Corrosion-resistant enclosures rated for salt-spray environments.

Certifications & Standards

Every unit is designed, tested, and certified to meet the most stringent international requirements.

ISO 9001
CE Marking
Type TestedKEMA / CESI available
UL ListingAvailable upon request
Compliance Standards:IEC 60076-11ANSI/IEEE C57.12.01GB/T 10228CSA C9

Case Studies

Proven performance in demanding real-world installations.

Singapore Data Centre Operator

Singapore

4 × 2.5 MVA, 22/0.4 kV, AN cooling, IP31

N+1 redundant configuration supplying critical IT load with fire-safe dry-type transformers co-located with server racks.

ChallengeSpace-constrained data hall with strict fire safety regulations. Traditional oil-filled units not permitted.
SolutionCompact cast-resin units with IP31 enclosure installed directly in the data hall, eliminating separate transformer rooms.
ResultZero safety incidents in 3+ years. Full-load efficiency of 99.2% exceeding Tier III requirements.

European Metro Operator

Germany

12 × 1.6 MVA, 10/0.4 kV, AN cooling, IP23

Underground station power supply with rigorous fire protection requirements for confined public spaces.

ChallengeStringent underground fire safety codes. Zero tolerance for liquid dielectric in tunnel environments.
SolutionVacuum-cast resin transformers with self-extinguishing epoxy, achieving F1 fire behaviour class per IEC 60076-11.
ResultApproved by TÜV for underground use. 5+ years continuous operation with zero maintenance interventions.

Optional Accessories & Upgrades

Enhance monitoring, cooling, and protection with purpose-built add-ons for your cast resin transformer.

Temperature Monitoring System

PT100 sensors with digital display and alarm contacts for winding and core temperature supervision.

Forced Air Cooling Kit

AF cooling fans with automatic start/stop control — boosts capacity by up to 40% during peak loads.

Protective Enclosure (IP54)

Weatherproof stainless steel enclosure for outdoor installation in coastal and industrial environments.

Online PD Monitoring

Continuous partial discharge monitoring system with IoT gateway for remote asset health tracking.

Technical Drawings & Downloads

Download product data sheets, outline drawings, installation manuals, and test reports.

Product Datasheet — Cast Resin Dry-TypePDF · 1.2 MB
Outline Drawing (Typical)DXF · 450 KB
Installation & Commissioning ManualPDF · 3.8 MB
Type Test Report (Sample)PDF · 2.1 MB

Interested in learning more?

Our engineering team is ready to provide detailed specifications, performance curves, and a tailored quotation for your requirements.

Request a Quote